Surge arrester ETITEC L1 DIN 002442985

Specifications

ETI Code:
002442985
Description:
ETITEC L1 DIN
Class name:
Surge arrester
Network system:
TT/TN-S
AC max continous operating voltage Uc:
320
Usage (IEC/VDE):
II, III / C, D
Current type:
AC
Function:
SPD
Rated voltage (V):
230
Type:
T2, T3
Short circuit capacity (kA):
10
Mounting:
DIN rail (top hat rail) 35 mm
Catalogue Group:
ETITEC LED
Up - Voltage protection level (kV):
1,5
Leakage current:
NO
Applied technology:
MOV+GDT
Max. discharge current Imax, 8/20 (kA):
10
In 8/20 (kA):
5
Installation:
LED Street lighting protection

Documents

Product

Net weight of the product
0.107  kg
Customs tariff
85363090  
logis_net_width
18  mm
logis_net_height
80  mm
logis_net_depth
38  mm

Basic packaging

Basic packaging quantity
1  
EAN code for a basic packaging
3838895829621  
Basic packaging weight
0.118  kg

Transport packaging

Transport packaging quantity
96  
EAN code for a transport packaging
3838895829638  
Transport packaging weight
13  kg
Pallet quantity
3840  

Intermediate packaging

qty
8  pcs
Weight
1.049  kg
Height (mm)
78  mm
Depth (mm)
183  mm
volume
1.499  dm3
Classification
EC000941
Class name
Surge protection device for power supply systems
Degree of protection (IP), front side
IP20
Rated voltage
230
Rated short-circuit breaking capacity according to EN 60898
10
Leakage current type
AC
System configuration DC
No
System configuration IT
No
System configuration TN-C
No
System configuration TN-S
Yes
System configuration TT
Yes
System configuration other
No
Nominal discharge surge current (8/20)
5
Nominal voltage AC
230
Short-circuit breaking capacity (Isccr)
10
Max. continuous voltage AC
320
Max. discharge surge current (8/20)
10
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
Other
Max. conductor cross section solid (solid, stranded)
2,5
Max. conductor cross section flexible (fine-strand)
2,5
With remote signalling contact
No
Integrated backup fuse
No
Signalling at the device
Optical
Category type 2
Yes
Degree of protection (IP)
IP20