Fuse link NHS2 gPV 200A/1000V DC 004110292

Specifications

ETI Code:
004110292
Description:
NHS2 gPV 200A/1000V DC
Class name:
Fuse link
Type:
NH-S
Size:
NH2
Rated current (A):
200
Rated DC voltage (V):
1000
Characteristics:
gPV
L/R (ms):
1
Breaking capacity DC (kA):
30
Application:
Fuse-link for DC application
Dimensions:
S110mm
Indicator:
Top fuse status indicator
Power dissipation (W):
26
Power dissipation (0,7x In) (W):
11
Operating joule integral (A2s):
29.000
Prearcing joule integral (A2s):
4.400
Standards:
IEC 60269-6

Documents

Product

Net weight of the product
650  g
Customs tariff
85361090  
logis_net_width
60  mm
logis_net_height
139  mm
logis_net_depth
60  mm

Basic packaging

Basic packaging quantity
1  
EAN code for a basic packaging
3838895799924  
Basic packaging weight
0.75  kg

Transport packaging

Transport packaging quantity
16  
EAN code for a transport packaging
3838895799931  
Transport packaging weight
12.24  kg
Pallet quantity
832  
Classification
EC000055
Class name
Low Voltage HRC fuse
Rated voltage DC
1000
Application
Fuse-link for DC application
Construction size
NH2
Rated current
200
Rated voltage
1000
Voltage type
DC
Rated switching capacity
30
Utilization category
Other
Type of fuse status indicator
Top fuse status indicator
Insulated metal gripping lugs (IMGL)
No
ETIM Classification – Version 7.0